Analog Input Scaling on ABB Totalflow

By NFM Consulting 1 min read

Key Takeaway

How to scale analog inputs on ABB Totalflow — raw-to-EU conversion, 4-20mA scaling, wire break detection, and calibration verification.

Quick Answer

Totalflow analog inputs produce 16-bit raw counts (0-65535). Configure input range (4-20mA) and engineering unit range (e.g., 0-1500 PSI) in PCCU32 for automatic linear scaling. Wire break detection alarms when the input drops below the 4mA live zero threshold.

Scaling Configuration

Set raw input range and EU range in the I/O configuration. Totalflow performs linear interpolation automatically. Scaled values are stored in registers used by flow calculation applications and reported to SCADA.

Wire Break Detection

Configure alarm below 4mA (typically 3.8mA equivalent). Triggers sensor fault alarm mapped to DNP3 for SCADA notification.

Calibration

Use PCCU32 trim functions (trim low at 4mA, trim high at 20mA) with a reference standard to calibrate each analog input channel. Document calibration for regulatory compliance.

For comparison, see SCADAPack analog scaling and Bristol FB300 analog scaling.