Energy Reporting in enteliWEB
Key Takeaway
How to use enteliWEB's energy reporting module for dashboards, KPI tracking, consumption analysis, EUI calculations, and energy report generation.
Quick Answer
enteliWEB includes a built-in energy reporting module that tracks building energy consumption via pulse meter inputs and BACnet accumulator objects. It provides dashboards with consumption bar charts, KPI gauges, EUI calculations, and exportable reports for energy management and benchmarking.
Metering Setup
Configure energy meter inputs — pulse counters for kWh meters and gas meters, or BACnet Accumulator objects from smart meters. Set the pulse scale factor (e.g., 1 pulse = 0.01 kWh) to convert raw counts to energy units.
Energy Dashboards
Build dashboard pages with consumption bar charts (daily, weekly, monthly), KPI gauges (current demand vs. target), and comparison widgets (this month vs. same month last year, building A vs. building B).
Energy Use Intensity (EUI)
EUI = annual energy consumption / building floor area, typically expressed in kBtu/sf/year. Configure building area in enteliWEB to enable automatic EUI calculation and benchmarking against industry standards.
Report Export
Generate energy reports as PDF or CSV. Schedule automated weekly or monthly reports delivered by email to facility managers. Reports can include consumption summaries, demand profiles, and degree-day normalized comparisons.
Frequently Asked Questions
Yes. enteliWEB aggregates data from multiple meters to provide submetering at the floor, zone, tenant, or system level.
Yes. When energy consumption and building floor area are configured, enteliWEB calculates and displays Energy Use Intensity (EUI) in kBtu/sf/year.