DNP3 Outstation Configuration on SCADAPack in Telepace Studio

By NFM Consulting 1 min read

Key Takeaway

How to configure a SCADAPack as a DNP3 Level 2 outstation — device addressing, data object mapping, unsolicited responses, event classes, and SCADA master integration.

Quick Answer

SCADAPack supports DNP3 Level 2 outstation on serial (RS-232/485) and Ethernet ports. Configure the outstation address in Telepace Studio, map I/O and registers to DNP3 data objects, assign event classes, and enable unsolicited responses for efficient SCADA communication.

DNP3 Configuration Steps

  1. Open Communications → DNP3 in the project tree
  2. Set the outstation address (1-65519)
  3. Select the communication port (serial or Ethernet)
  4. Map data objects:
    • Binary Inputs (Object 1/2) ← digital inputs, status bits
    • Analog Inputs (Object 30/32) ← scaled analog values
    • Counters (Object 20/22) ← pulse accumulators
    • Binary Outputs (Object 10/12) ← digital output control
    • Analog Outputs (Object 40/42) ← analog setpoints
  5. Assign event classes (Class 1=alarms, Class 2=process, Class 3=status)
  6. Enable unsolicited responses for push-based reporting

Testing

Test with Geo SCADA or Ignition as the DNP3 master. Verify integrity poll responses, event reporting, and control output operation.

For comparison, see Bristol FB300 DNP3 configuration.