SEL Real Time Automation Controller (RTAC) Overview
Key Takeaway
What the SEL RTAC is — substation data concentrator, protocol gateway (SEL/DNP3/Modbus/IEC 61850), IEC 61131-3 automation controller, and NERC CIP security platform.
Quick Answer
The SEL RTAC (Real Time Automation Controller) is a substation automation controller that aggregates data from multiple relays via SEL protocol, DNP3, Modbus, and IEC 61850, presents it to the SCADA master (typically as a DNP3 outstation), and runs IEC 61131-3 control logic for substation automation. Current platforms include SEL-3530-4, SEL-3350, SEL-3555/3560, SEL-3505, and Axion (full-rack SEL-3530 is legacy; SEL-3354 is a computer, not an RTAC). ICCP/TASE.2 is not an RTAC protocol — control-center ICCP links (e.g., QSE to ERCOT) sit upstream of the substation RTAC.
Functions
- Protocol gateway — SEL ↔ DNP3 ↔ Modbus ↔ IEC 61850 (plus IEC 60870-5-101/104 and other SEL-supported clients/servers)
- Data concentrator — Aggregates data from multiple relays to one SCADA point
- Automation controller — IEC 61131-3 logic (Ladder, Structured Text, Continuous Function Chart)
- Optional web HMI — Local substation operator display via Diagram Builder (SEL-5035)
- Event log aggregator — Centralized event collection
Programming
ACSELERATOR RTAC (SEL-5033) provides IEC 61131-3 programming. Common languages: Structured Text and Function Block Diagram. See Allen-Bradley ST and Ignition for cross-platform comparison.
Applications
- Substation data concentration for utility SCADA
- Automatic bus transfer (ABT)
- Load shedding automation
- Volt/VAR optimization
Need help with scada & programming?
Texas-based licensed engineers — get a free, no-obligation assessment.
Frequently Asked Questions
Substation data concentration, protocol gateway translation, IEC 61131-3 automation logic, and local HMI — bridging relays to SCADA.
Ladder Diagram, Structured Text, and Continuous Function Chart (CFC). SFC and Instruction List are not listed RTAC editors.
Yes. Common application: IEC 61850 MMS client reading modern IEDs while presenting data to a legacy DNP3 SCADA master.